Three Sensor Data Output Types
Sensors can provide measurement data through digital, analog, or switch outputs. The appropriate output type depends on factors such as transmission distance, electromagnetic interference, terrain, control-system compatibility, and whether continuous measurement data or threshold-based signals are required.
| Output Type |
Available Forms |
Typical Application |
| Digital output |
RS232, RS485, or wireless transmission |
Transmission of digital measurement data to a computer, controller, or monitoring system |
| Analog output |
4–20 mA or 0–10 V |
Continuous distance measurement using a current or voltage signal |
| Switch output |
Up to two relay outputs |
Threshold detection and event-triggered control |
1. Digital Output
Digital-output sensors are available with RS232, RS485, or wireless transmission. Selection should be based primarily on the required transmission distance, the level of electromagnetic interference, and the complexity of the installation environment.
| Digital Output |
Transmission Characteristics |
Recommended Use |
| RS232 |
Generally suitable for distances within 10 m; relatively weak resistance to electromagnetic interference |
Short-distance data transmission in environments with limited interference |
| RS485 |
Suitable for longer-distance transmission, typically up to 1,000 m; stronger resistance to electromagnetic interference |
Industrial installations requiring reliable long-distance communication |
| Wireless transmission |
Does not require a continuous wired connection between transmission points |
Complex terrain or locations where cable installation is difficult |
2. Analog Output
Analog-output sensors provide either a 4–20 mA current signal or a 0–10 V voltage signal. The output changes continuously with the measured distance, and each current or voltage value corresponds to a specific distance value within the configured measurement range.
4–20 mA Output Example
For example, the JGS-30A distance sensor has a measurement range of 0.2–30 m. Under its default current-output configuration:
- 4 mA corresponds to 0.2 m (200 mm).
- 20 mA corresponds to 30 m (30,000 mm).
The relationship between output current I and measured distance L is:
L = (I − 4) / Δi + 200
Where:
Δi = (20 − 4) mA / (30,000 − 200) mm
| Symbol |
Description |
Unit |
| L |
Calculated distance |
mm |
| I |
Measured output current |
mA |
| Δi |
Current change per millimeter over the configured range |
mA/mm |
The analog output endpoints can be configured in either of the following ways:
- Factory preset: The manufacturer sets the distance values corresponding to the minimum and maximum analog outputs according to the user’s requirements. In this configuration, users cannot modify the values themselves.
- User-configurable: The configuration interface is made available so that users can set the corresponding distance values with dedicated setting software.
This applies to endpoint settings such as the distance represented by 4 mA and 20 mA, or by the minimum and maximum values of a voltage-output range.
3. Switch Output
Switch-output sensors support up to two sets of relay outputs. Each relay can correspond to a preset distance threshold. When the measured distance reaches the configured value, the corresponding output terminal disconnects.
| Item |
Description |
| Number of outputs |
Up to two relay switch outputs |
| Trigger condition |
The measured distance reaches the preset threshold |
| Output action |
The corresponding output terminal disconnects |
| Threshold configuration |
Factory preset or user-configurable through dedicated setting software |
As with analog-output settings, relay thresholds can be preset by the manufacturer according to the user’s requirements. If the configuration interface is left open, users can modify the thresholds using specialized setting software.
Output Type Selection Summary
- Select RS232 for short-distance digital communication within 10 m where electromagnetic interference is limited.
- Select RS485 for longer transmission distances, typically up to 1,000 m, or where stronger interference resistance is required.
- Select wireless transmission for complex terrain or installations where wiring is impractical.
- Select a 4–20 mA or 0–10 V analog output when continuous distance values must be transmitted to a compatible control or monitoring system.
- Select a relay switch output when the application only needs to respond after the measured distance reaches one or two preset thresholds.
